Closed Cell Elastomeric Insulation

Isoline


When fire tested Isoline does not generate flaming droplets, has no flame spread and has a low fire propagation index.
These combined meet the fire performance requirement of Class O as in Building Regulations.
Further guarantee is given by supervision contracts with independent European laboratories.


Isoline closed cell elastomeric insulation has a high diffusion resistance factor m that minimzes water vapour penetration, giving excellent long term performance.

 

Isoline thermal conductivity is l 0 oC = 0.035 W/mK .
The thermal conductivity is the most important factor in calculation fousec on energy saving.

 

 

 

Isoline Sheet rolls

Type Thickness Sheet 1 metre wide Sheet 1.5 metre wide
mm inches format m2/box format m2/box
PL/RO 06 6 1/4" 30 X 1 30 30 X 1.5 45
PL/RO 10 10 3/8" 20 X 1 20 20 X 1.5 30
PL/RO 13 13 1/2" 14 X 1 14 14 X 1.5 21
PL/RO 16 16 5/8" 12 X 1 12 12 X 1.5 18
PL/RO 19 19 3/4" 10 X 1 10 10 X 1.5 15
PL/RO 25 25 1" 8 X 1 8 8 X 1.5 12
PL/RO 32 32 1 1/4" 6 X 1 6 6 X 1.5 9
PL/RO 50 50 2" 4 X 1 4 4 X 1.5 6
   

Isoline Sheet flat

Type Thickness 2m x 1m sheet 2m x 0.5m sheet
mm inches m2/box m2/box
PL 06 6 1/4" 48 24
PL 10 10 3/8" 32 16
PL 13 13 1/2" 24 12
PL 16 16 5/8" 20 10
PL 19 19 3/4" 16 8
PL 25 25 1" 12 6
PL 32 32 1 1/4" 10 5
PL 50 50 2" 6 3
Data sheet
Thermal conductivity DIN 52613 DIN 52612 B5874 part 2 1986 l -20oC = 0.033 W/mK l 0oC = 0.035 W/mK l+20oC = 0.037 W/mK
Temperature range pipes -45 oC to + 116 oC sheet -45 oC to + 85 oC
Water vapour diffusion resistance factor DIN52615

ISO9346

> m 7000
Water vapour permeability BS 4370 DIN52165 0.09 mgm/N.h.
Water absorption % by volume after 28 days < 1.1
Flexibilty Excellent
Ozone resistance Good
Wall penetration standard fire test Up to 180 minutes conditions similar to BS476 part 20 1987
Resistance to oil and greases Good
Resistance toU.V.and weather Good *
Odour Negligible
Reaction to fire:

B.S. 476 Part 7 1979

Ignitability:

BS 476 Part 7 1987

Surface spread of flame fire propagation:

B.S. 476 Part 6 1989

Class P

Class 1

Class 0 *

Italy CSE RF 3/77 France Class 1 supervised M1-NF supervised
DIN 1988/7 corrosion risk Meet limit values
Noise reduction DIN4109 up to 32db (A)
Density 65 to 80 Kg/m3

4 lb/ft3 to 5 lb/ft3

% closed cells > 90
* Outdoor applications should be painted with isoline paint to the recommened thickness. Two or more coats may be required.